PP & PPR - Technical Specifications

ELECTRICAL SPECIFICATIONS
  Q100 model Q300 model Q500 model
Output Max current per towerPP 550/1650A 1700/5100A 8000/24000A
PPR250(750)A 1100(3300)A 5000(15000)A
VoltagePP 5-450VDC
PPR 5-50VDC
Max. pulsed current Up to 3 times the max DC current value depending on the pattern required
Operation Mode Current control or Voltage Control (limited)
Control accuracy 1/1000 of max current or voltage
Current regulation range 2 - 100% of max current (With CTRD02)
Voltage regulation range 5 - 100% of max voltage (With CTRD02)
Current ripple (RMS) < 2.0% of rated output current in current operation mode (< 1.0% on Request)
Efficiency 89% (typ.) @ rated load / 92% (for >= 160VDC) @ rated load
Min. Pulse duration Slow: 3ms | Fast: 1ms
Secondary withstand voltage 50VAC 50Hz 1min. between Secondary to earth
Pole to be connected to ground Positive
Main
Supply
Line voltage 3 x 230VAC ± 10%, 3 x 400VAC ± 10%, 3 x 440VAC ± 10%,
3 x 480VAC ± 10% or 3 x 550VAC ± 10% or 3 x 575VAC ± 10%
Frequency 50 - 60Hz
Neutral NOT USED
Power factor > 95% @ rated load
Primary current in max DC Max 20A Max 55A Max 230A per tower
Earth leakage current See EMC filter input specifications

GENERAL SPECIFICATIONS
 
Q100 model
Q300 model
Q500 model
Technology
Switching mode PWM, Full Bridge IGBT inverter
Cooling Systems
Air
Water
Operation
Conditions
Location
Indoor use only
Ambient temperature
0 - 40°C (up to 50°C with 15% derating -air cooled- / 10% derating -water cooled-)
Relative humidity
15 - 85% not condensing
Filter obstruction - air cooled
15% max
Water input temp. - water cooled
19 - 22°C (rectifier rev. A1-A49) | 19 - 28°C (rectifier rev. A60 or above)
Altitude
<= 2000m
Degree of Protection
Air cooled
IP31
IP21 (on request NEMA12)
IP32
Water cooled
IP43
-
IP42 (on request IP65)
Enclosuer color
RAL 3004
RAL 5010
RAL 3004
Conformity of EU Directives
2006/95/EC - Low Voltage Directive
2004/108/EC - Electromagnetic Compatibility

PROTECTION
Surge
According to DirectiveEN 61000-4-5
2kV between each input phase and PE. 1kV across each input phase combination.
Phase Loss
TypeHardwareSoftware
Programmed limitHalf cycleAdjustable via configuration parameter
 
Output Short Circuit
TypeSoftware
Programmed limit25% of Iout_max
Detection Time1ms
Thermal Protection
With PTC on each module

SERIAL INTERFACE
Communication Ports
RS232
RS485
Communication Protocols
CRS-ASCIIIncludedRS232 point-to-point and RS485 network
Modbus-RTUIncludedRS232 point-to-point and RS485 network
Profibus-DPOptional with additional boardProfibus-DP network
DeviceNetOptional with additional boardCAN bus network
Modbus/TCPOptional with additional boardEthernet
ProfinetOptional with additional boardEthernet
EthernetIPOptional with additional boardEthernet

FULL LOAD HARMONICS DISTORTION
Harmonic
Freq. (Hz)
Absorbed Current Distortions
3
150
-
5
250
< 22.5%
7
350
< 12.5%
9
450
-
11
550
< 11.0%
13
650
< 7.6%
17
850
< 8.0%
19
950
< 4.8%
THD
MAX 30%